| 2019-08-28 17:08:37 | PROVISO COMPLY BEFORE FIRST INSPECTION |
| | |
| | |
| | 1. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT |
| | 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS |
| | LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI |
| | IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS |
| | APPLIANCES. PER FBC FG 410.2 |
| | |
| | 2. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON |
| | THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED |
| | ONLY THE BUILDING SIDE OF THE METER IS REQUIRED |
| | |
| | DUE TO THE LACK OF INFORMATION ON WATER HEATER THE |
| | FOLLOWING COMMENTS SHALL BE ADDRESSED |
| | |
| | 3. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR WATER |
| | HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS |
| | ISSUED. CAN NOT BE DIFFERED SUBMITTAL |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES. |
| | SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT |
| | VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY. |
| | |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, |
| | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL |
| | GAS CODE SEC. 502 THRU 505. |
| | |