| 2019-06-04 10:08:14 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110093 |
| | 6/4/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A0.02, M-101, & M-102: IT APPEARS THAT SMOKE |
| | DAMPERS MAY BE MISSING FOR DUCTS PENETRATING SMOKE |
| | PARTITIONS. PLEASE REVISE THE LIFE SAFETY PLANS TO |
| | CLEARLY SHOW THE LOCATIONS OF ALL SMOKE PARTITIONS, AND |
| | REVISE THE MECHANICAL PLANS TO SHOW THE SMOKE DAMPER |
| | LOCATIONS (IF APPLICABLE)- SEE SECTION 607.5.7 FBC M. |
| | |
| | 2) M-102: THE PLANS ARE STILL NOT CLEARLY INDICATING |
| | HOW COMBUSTION AIR AND VENTING FOR THE GAS WATER HEATER |
| | WILL BE ACCOMPLISHED. THERE IS ONE NEW EXTERIOR WALL |
| | CAP THAT IS NOTED AS WH EXHAUST AIR AND COMBUSTION |
| | MAKEUP AIR. TYPICALLY DIRECT VENTS TERMINATE AT THE |
| | EXTERIOR OF THE BUILDING AND DO NOT REQUIRE A WALL CAP. |
| | IS THIS A CONCENTRIC VENT THAT WEILL BE BRINGING IN THE |
| | COMBUSTION AIR? IT MAY BE HELPFUL TO PROVIDE A DETAIL |
| | OR ENLARGED DRAWING. PLEASE NOTE THAT IF COMBUSTION IS |
| | TO BE BROUGHT IN THOUGH THE OPENING, IT SHALL BE SIZED |
| | AND LOCATED IN ACCORDANCE WITH SECTION 304.6.2 FBC FG. |
| | |
| | 3) PLEASE PROVIDE A MASTER LIST ON THE PLAN OF ALL |
| | REQUESTED DEFERRED SUBMITTALS INCLUDING, BUT NOT |
| | LIMITED TO: |
| | |
| | A) KITCHEN EQUIPMENT PLANS AND SCHEDULES INCLUDING |
| | PRODUCT DATA SHEETS FOR GAS-FIRED COOKING APPLIANCES. |
| | B) KITCHEN HOOD AND EXHAUST SYSTEM PLANS |
| | C) FIRE SUPPRESSION PLAN. |
| | D) WALK-IN COOLER AND FREEZER PLANS. |
| | E) GENERATOR |
| | G) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION |
| | OF THE CHILLER AND ALL OTHER EXTERIOR MECHANICAL |
| | EQUIPMENT AND COMPONENTS. |
| | H) FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOAS FOR THE |
| | EXHAUST AND O/A LOUVERS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |