| Date |
Text |
| 2019-04-24 09:28:37 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110093 |
| | 4/24/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN ACCORDANCE WITH THE ARCHITECT'S NARRATIVE, THE |
| | KITCHEN COOKING APPLIANCES AND EQUIPMENT, THE KITCHEN |
| | HOODS AND FIRE SUPPRESSION SYSTEMS WILL BE DONE UNDER |
| | SEPARATE PERMIT. AS A RESULT, THE NARRATIVE INDICATES |
| | GAS-FIRED COOKING APPLIANCE SUBMOTTALS, COMBUSTION AIR |
| | CALCULATIONS, AIR BALANCE CALCULATIONS, AND MAKE UP AIR |
| | TEMPERATURE COMPLIANCE WILL ALSO BE DEFERRED TO A |
| | FUTURE DATE. PLEASE PLACE LARGE BOLD NOTES ON THE PLAN |
| | TO INDICATE THIS FOR PUBIC RECORD AND FOR THE |
| | CONTRACTORS IN THE FIELD. |
| | |
| | 2) CLARIFY IF THE GENERATOR IS TO BE UNDER SEPARATE |
| | PERMIT. IF SO, PLEASE ADD IT TO THE LIST OF DEFERRED |
| | SUBMITTALS LISTED IN COMMENT #1. OTHERWISE, COMPLY WITH |
| | ITEMS A-F LISTED BELOW: |
| | |
| | A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE, MUFFLER, |
| | AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION |
| | 304.1 FBC M. |
| | |
| | B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE |
| | GENERATOR- SECTION 915.1 FBC M. THE MANUFACTURER'S |
| | SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE |
| | GENERATOR IS IN COMPLIANCE WITH NFPA 37. |
| | |
| | C) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FUEL |
| | TANK THAT INCLUDES THE TANK'S UL LISTING- UL 142 OR UL |
| | 2085- SEE SECTION 21.4.2.1.1 NFPA 30. |
| | |
| | D) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL |
| | SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION |
| | LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL |
| | AIR INTAKES INTO THE BUILDING PLEASE INCLUDE ALL |
| | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE |
| | SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. |
| | |
| | E) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND |
| | EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT |
| | PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13 |
| | NFPA 30. |
| | |
| | F) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE |
| | GENERATOR TO THE STRUCTURAL SLAB- SECTION 301.15 FBC M. |
| | |
| | 3) SHEET M-102: AS PREVIOUSLY NOTED IN THE 1ST REVIEW, |
| | THE SUPPLY DUCT AND DIFFUSER ARE PROHIBITED FROM |
| | PENETRATING INTO THE INTERIOR EXIT STAIRWAY- SECTIONS |
| | 1023.5 & 1023.6 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |