| 2019-04-19 08:19:14 | 2ND REVIEW: 18110093 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | |
| | |
| | GAS COMMENTS:2ND REQUEST |
| | |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH |
| | TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL |
| | NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED, |
| | PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE |
| | PIPE. |
| | |
| | 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT |
| | 2"WG AND PRESSURE DROP OF 3"WG IT GIVES A TABLE WHICH |
| | IS LESS THAN 2 PSI AND PRESSURE DROP OF 6"WC PLEASE |
| | CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. WHAT DOES |
| | WG STAND FOR IS IT WATER COLUMN IF THATS THE CASE 2"WC |
| | IS VERY LOW I'LL NEED TO SEE THE MANUFACTURE SPEC TO |
| | VERIFY THAT IS SUFFICIENT. |
| | |
| | |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | SHOW ON RISER |
| | |
| | |
| | 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS |
| | ISSUED. |
| | |
| | 10.FIRST SECTION OF PIPE AFTER METER IS UNDER SIZED IT |
| | SHOULD BE 11/4" TO MATCH PIPING UPSTREAM. PER FBC FG |
| | TABLE 402.3(3) WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 11. SHT. P-902 KEY NOTE #4 WHAT IS AN ACCEPTANCE TANK |
| | PLEASE CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | PLEASE CHANGE PLAN TO THERMAL EXPANSION TANK SO THAT |
| | THE FIELD INSPECTOR CAN VERIFY COMPLIANCE. |
| | |
| | NEW COMMENT |
| | |
| | 1. THE VALVE FOR FUTURE PIPING SHALL BE LOCKOUT TYPE |
| | PLEASE PROVIDE A DETAIL OR NOTE THAT THE FUTURE PIPING |
| | SHALL BE CAPPED AND HAVE A LOCK OUT VALVE.PER WPB |
| | AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |