| Plan Review Notes For Permit 18110093 |
| Permit Number |
18110093 |
|
| Review Stop |
P-GREASE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-18 10:37:36 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS FOR GREASE INTERCEPTOR: | | | | | | 1. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER | | | FBC PL 1003.2 | | | | | | 2. THE MOP SINK IN THE KITCHEN AREA SHALL BE INCLUDED | | | ON THE GREASE PIPING AND SIZING CALCULATIONS. PER FBC | | | PL 1003.3.1 | | | | | | 3. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|