| | 1ST REVIEW: 18110093 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE BATHROOM OPENING INTO THE KITCHEN PREP AREA IS A |
| | CODE VIOLATION. TOILET ROOMS SHALL NOT OPEN DIRECTLY |
| | INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR |
| | SERVICE TO THE PUBLIC. PER FBC PL 403.3.2 |
| | |
| | 2. IN THE MULTI USER BATHROOMS AT LEAST ONE LAVATORY |
| | SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A |
| | TOILET COMPARTMENT. PER FBC ACC 213.3.4 |
| | |
| | 3. SHT A4.07 DETAIL 1 THE 36" INSIDE DIMENSION FOR THE |
| | TRANSFER SHOWER IS NOT A MINIMUM IT SHALL BE AN EXACT |
| | 36" CLEAR INSIDE DIMENSION. PER FBC ACC 608.2.1 |
| | |
| | 4. PROVIDE A LEGEND FOR THE CLEAR FLOOR SPACE AROUND |
| | THE ACCESSIBLE FIXTURES OR SHOW DIMENSIONS ON EACH |
| | SPACE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. A4.07 DETAIL ONE SHOW A 60X56" CLEAR FLOOR |
| | SPACE FOR THE TOILET AND A 36"X48" IN FRONT OF THE |
| | SHOWER WITH 1 END LINED UP WITH CONTROL WALL. PER FBC |
| | ACC 604.3.1, 608.2.1 |
| | |
| | 6. SHT. A4.07 DETAIL B IS SHOWING A 2'-6" MIN DIMENSION |
| | FOR THE SHOWER IT SHALL BE 36". PER FBC ACC 608.2.1 |
| | |
| | 7. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE |
| | SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A |
| | POINT WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE TOP |
| | OF THE SEAT SHALL BE 17 INCHES MINIMUM AND 19 INCHES |
| | MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL |
| | COMPLY WITH 610.3.1 OR 610.3.2. |
| | |
| | 8. SHT. P-105 IT APPEARS THE WATER PIPING RUNNING UNDER |
| | THE SLAB TO THE BAR IS MISSED LABELED THE KEY NOTE |
| | STATES IT AT #4 THE PIPING SHOWS #3 PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. PROVIDE FIRE STOPPING DETAILS FOR PLASTIC PIPING. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT.P-901 PLEASE REMOVE GAS PING FROM WATER |
| | ISOMETRIC IT IS TO CONGESTED. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 11. SHT P-901 PLEASE SHOW THE FOLLOWING ON THE |
| | ISOMETRIC THE FLOOR LEVELS, VALVES ON THE DROPS AND |
| | BRANCHES AND LABEL THE FIXTURES. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 12. SHT P-906 IN ADDING UP ALL THE SQFT I CAME OUT WITH |
| | 2554 WHICH MAKES THE HORIZONTAL PIPING UNDER SIZED 6" |
| | SHOULD RUN TO THE 4TH BRANCH FROM THE END PLEASE SHOE |
| | SQFT TABLES ON THE PIPING AND INDICATE WHAT SLOPE THE |
| | PIPING WILL BE INSTALLED. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 13. THE SANITARY SYSTEM SERVING THE BAR SHALL HAVE A |
| | MINIMUM OF 1 VENT EXTENDING TO THE OUTDOORS. PER FBC PL |
| | 904.1, 904.1.1 |
| | |
| | 14. SHT. P-904 KEY NOTE #4 LIST A 3" VENT THE VENT FOR |
| | THE GREASE SYSTEM IS TAGGED #4 BUT IS SIZED AS 2" |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 15. SHT. P-904 THE VENT SHOWN BY ITSELF NEXT TO THE 2ND |
| | + 3RD FLOOR BATHROOM ISOMETRIC IS TAGGED AS #6 IT IS |
| | SIZED AT 2" THE KEY NOTE #6 LIST IT AT 3" PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 16. ALL VENTS SHALL COMPLY WITH FBC PL TABLE 906.1, |
| | 906.2 |
| | |
| | 17. SHT. P-904 ON THE ISOMETRIC FOR THE GREASE WASTE |
| | SYSTEM THE FLOOR SINK APPEARS TO BE MISLABELED AS THE |
| | FLOOR DRAIN AND THE FLOOR DRAIN IS NOT LABELED PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 18. SHT. P-904 PLEASE SHOE P-TRAP ON ALL FLOOR DRAINS |
| | AND INDICATE TRAP PRIMER. PER FBC PL 1002.1, 1002.4.1 |
| | |
| | 19. SHT. P-902 PLEASE SHOW SHUT OFF VALVES ON THE DROPS |
| | AND BRANCHES. PER FBC PL 606.1 |
| | |
| | 20. SHT. P-902 INDICATE ON THE ISOMETRIC A TEMPERATURE |
| | LIMITING DEVISE COMPLYING WITH ASSE 1070 IS REQUIRED ON |
| | THE LAVATORY'S IN THE BATHROOMS. PER FBC PL 416.5 |
| | |
| | 21. SHT. A-4.07 GRAB BARS SHALL BE MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE FROM FINISHED FLOOR PER FBC ACC |
| | 609.4 |
| | |
| | 22. SHT. P-902 LABEL UNDERGROUND PIPING ON WATER AND |
| | GAS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 23. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER |
| | FBC PL 1003.2 |
| | |
| | 24. THE MOP SINK IN THE KITCHEN AREA SHALL BE INCLUDED |
| | ON THE GREASE PIPING AND SIZING CALCULATIONS. PER FBC |
| | PL 1003.3.1 |
| | |
| | 25. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |