Plan Review Notes
Plan Review Notes For Permit 18110072
Permit Number 18110072
Review Stop M
Sequence Number 3
Notes
Date Text
2018-11-30 15:44:592ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110072
 11/30/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME COMMENTS FROM THE 1ST REVIEW HAVE NOT COMPLETELY
 ADDRESSED- SEE BELOW.
  
 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE
 EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION
 508.1.2 FBC M. ( THE ENGINEER IS STATING IN THE COMMENT
 RESPONSE NARRATIVE THAT MAKE UP AIR IS PROVIDED BY THE
 FOOD COURT, HOWEVER THE DRAWINGS IINDICATE THAT THE
 HOOD IS IN THE BACK OF HOUSE AREA AND NOT IN A LOCATION
 OPEN TO THE FOOD COURT. ALSO THE REQUESTED AIR BALANCE
 CALCULATION WAS NOT PROVIDED)
  
 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. (COMPLIANCE
 WILL DEPEND ON HOW MAKEUP AIR WILL BE PROVIDED PER
 COMMENT #9 ABOVE).
  
 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 ROOFTOP CURB AND FAN- SECTION 301.15 FBC M. ( PLEASE
 PROVIDE COMPLETE ENGINEERING ON THE PLAN INCLUDING THE
 DESIGN CRITERIA, AND/OR A COMPLETE FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE EXHAUST FAN THAT
 INCLUDES THE COVER SHEET THAT BEARING EITHER THE
 CURRENT PRODUCT APPROVAL OR NOA NUMBER.)
  
 1) NEW COMMENT- SHEET A1.0: THE RETURN AIR GRILLES MUST
 BE LOCATED A MINIMUM OF 10' FROM THE COOKING APPLIANCE
 UNDER THE HOOD
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  