| 2018-11-30 15:44:59 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110072 |
| | 11/30/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SOME COMMENTS FROM THE 1ST REVIEW HAVE NOT COMPLETELY |
| | ADDRESSED- SEE BELOW. |
| | |
| | 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE |
| | EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION |
| | 508.1.2 FBC M. ( THE ENGINEER IS STATING IN THE COMMENT |
| | RESPONSE NARRATIVE THAT MAKE UP AIR IS PROVIDED BY THE |
| | FOOD COURT, HOWEVER THE DRAWINGS IINDICATE THAT THE |
| | HOOD IS IN THE BACK OF HOUSE AREA AND NOT IN A LOCATION |
| | OPEN TO THE FOOD COURT. ALSO THE REQUESTED AIR BALANCE |
| | CALCULATION WAS NOT PROVIDED) |
| | |
| | 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR |
| | TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| | NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE |
| | ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO |
| | NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. (COMPLIANCE |
| | WILL DEPEND ON HOW MAKEUP AIR WILL BE PROVIDED PER |
| | COMMENT #9 ABOVE). |
| | |
| | 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE |
| | ROOFTOP CURB AND FAN- SECTION 301.15 FBC M. ( PLEASE |
| | PROVIDE COMPLETE ENGINEERING ON THE PLAN INCLUDING THE |
| | DESIGN CRITERIA, AND/OR A COMPLETE FLORIDA PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA FOR THE EXHAUST FAN THAT |
| | INCLUDES THE COVER SHEET THAT BEARING EITHER THE |
| | CURRENT PRODUCT APPROVAL OR NOA NUMBER.) |
| | |
| | 1) NEW COMMENT- SHEET A1.0: THE RETURN AIR GRILLES MUST |
| | BE LOCATED A MINIMUM OF 10' FROM THE COOKING APPLIANCE |
| | UNDER THE HOOD |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |