Plan Review Notes
Plan Review Notes For Permit 18110072
Permit Number 18110072
Review Stop M
Sequence Number 2
Notes
Date Text
2018-11-14 15:25:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110072
 11/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A COMPLETE SET OF BURGER KING BUILDING PLANS HAVE
 BEEN SUBMITTED FOR REVIEW OF A KITCHEN HOOD EXHAUST
 PROJECT. PLEASE REMOVE ALL PLAN SHEETS NOT ASSOCIATED
 WITH THE HOOD INCLUDING THE ARCHITECTURAL, PLUMBING,
 AND ELECTRICAL SHEETS AND RESUBMIT THE H-1, H-2, H-3
 SHEETS THAT ARE INCLUDED WITH THE SETS, ALONG WITH THE
 K-1, K-2, AND K-3 SHEETS THAT WERE NOT INCLUDED IN THE
 SETS, BUT ARE LISTED IN THE INDEX ON THE COVER SHEET
 CS- SECTIONS 107.1 & 107.2.1 WPB
  
 2) PROVIDE A DUPLICATE SET OF FRANKECANOPY HOOD SHOP
 DRAWINGS (ONLY ONE SET WAS SUBMITTED). EACH SET SHALL
 BEAR THE APPROVAL STAMP OF THE ENGINEER OF RECORD-
 SHANER HAMILITON P.E ( SEE SHEETS H-1, H-2, AND H-3).
  
 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 SUPPRESSION SYSTEM, AND THE NEW BROILER- SECTIONS 107.1
 & 107.2.1.3 WPB.
  
 4) THE $10,000.00 VALUE LISTED ON THE APPLICATION IS
 LOW. PERMIT VALUE IS BASED ON LABOR, MATERIALS, AND
 EQUIPMENT REGARDLESS OF WHO PURCHASES THE EQUIPMENT AND
 MATERIALS. PLEASE PROVIDE SIGNED CONTRACTS AND INVOICES
 TO VERIFY TOTAL COSTS- SECTION 109.3 WPB.
  
 5) SHEET H-2: INDICATE THE TERMINATION HEIGHT OF THE
 EXHAUST FAN OUTLET ABOVE THE FINISHED ROOF- SEE SECTION
 506.3.13.1 FBC M.
  
 6) H-2: CLARIFY WHICH GREASE DUCT WRAP WILL BE
 INSTALLED, AND SUBMIT SPECS FOR THE CORRECT ONE. THE
 NOTES ON THE PLAN CALL OUT 3M AND THE LEGEND CALLS OUT
 FIREMASTER- TWO DIFFERENT BRANDS- SECTION 506.3.11.2
 FBC M.
  
 7) H-2: PROVIDE AN EXHAUST HOOD SCHEDULE ON THE PLAN
 THAT LISTS THE MAKE AND MODEL, MAX COOKING TEMP, TOTAL
 EXHAUST CFMS, TOTAL SUPPLY CFMS, AND HOOD DIMENSIONS-
 107.2.1 WPB.
  
 8) H-2: INDICATE THE TYPE AND SIZE OF GREASE EXHAUST
 DUCT- THE PLAN INDICATES "BY OTHERS" WHICH IS
 UNACCEPTABLE FOR PERMITTING. REMOVE THE NOTE AND REFER
 TO SECTION 506.3.1.1 FBC M FOR DUCT MATERIAL
 REQUIREMENTS.
  
 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE
 EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION
 508.1.2 FBC M.
  
 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 ROOFTOP CURB AND FAN- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  