| 2019-01-22 15:53:23 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR | | | THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE | | | MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC | | | 1609.1 | | | | | | 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS | | | THAT WILL BE USED TO SECURE THE GENERATOR TO THE | | | GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1 | | | | | | 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION | | | MANUAL FOR THE GENERATOR. FBC 107.2.1 |
|