| Date |
Text |
| 2018-12-11 11:55:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THIS INSTALLATION SHALL ME THE REQUIREMENTS OF NFPA |
| | 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY |
| | COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION |
| | |
| | THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS |
| | ALONG THE WALL OF THE STRUCTURE. |
| | |
| | 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR |
| | WEATHERPROOF |
| | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS |
| | SHALL |
| | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS |
| | AND AT |
| | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE |
| | WALLS. A |
| | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER |
| | OF THE |
| | FOLLOWING CONDITIONS EXIST: |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 |
| | M (5 FT) |
| | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING |
| | OF |
| | AT LEAST 1 HOUR. |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE |
| | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE |
| | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS |
| | OUTSIDE THE ENCLOSURE. |
| | |
| | |
| | PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL |
| | OPENINGS ALONG THE WALL OF THE STRUCTURE. |
| | |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OR DIMESNION FROM THE |
| | PROPERTY LINE OR STRUCTURE IN THE ADJACENT STRUCTURE |
| | AND THE OPEINGS ALONG THAT STRUCTURE. |
| | |
| | PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY. |
| | |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT |
| | AREA OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT |
| | IS NEXT TO. |
| | |
| | EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE |
| | FROM THE OVERHANG OR SOFFITT AREA, |
| | |
| | |
| | 8.2.3 EXHAUST SYSTEM TERMINATION. |
| | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE |
| | STRUCTURE |
| | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF |
| | COMBUSTION |
| | WILL DISCHARGE TO A SAFE LOCATION. |
| | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE |
| | DIRECTED TOWARD |
| | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES |
| | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR |
| | COMBUSTIBLE |
| | DUSTS. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY |
| | POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER |
| | ALARM SYSTEMS. |
| | |
| | IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR |
| | EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION |
| | |
| | PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS |
| | AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |