| 2018-12-08 13:16:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. NO INFORMATION WAS PROVIDED - OCCUPANCY |
| | CLASSIFICATION FBC B CHAPTER 3, RESISTANCE TO WIND |
| | (BOTH ANCHORING AND THE PROPOSED STRUCTURE), FBC B |
| | 1609. WHAT WILL BE STORED IN THE SHIPPING CONTAINER? |
| | SHIPPING CONTAINERS ARE DESIGNED TO BE LOADED WITH |
| | MATERIAL AND SHIPPED, WHICH DOES NOT APPEAR TO BE THE |
| | PROPOSED USE UNDER THIS PERMIT. IF THIS IS FOR STORAGE |
| | OF EQUIPMENT (SUCH AS LAWNMOWERS, OTHER MAINTENANCE |
| | EQUIPMENT), PROVIDE A PLAN WHICH CLEARLY SHOWS PROPOSED |
| | USE. |
| | |
| | PER FS471, ENGINEERING WILL BE REQUIRED TO DEMONSTRATE |
| | WIND RESISTANCE. IT IS NOT CLEAR IF A DESIGN |
| | PROFESSIONAL WILL BE REQUIRED FOR OTHER PLANS AS SCOPE |
| | HAS NOT BEEN DETERMINED. |
| | |
| | A SITE PLAN IS REQUIRED SHOWING DISTANCE TO PROPERTY |
| | LINE AND ASSUMED PROPERTY LINE, SEE FBC B CHAPTERS 6 |
| | AND 7. BUILDING CONSTRUCTION TYPE, OPENINGS, FIRE |
| | RESISTANCE (IF APPLICABLE) INFORMATION NOT PROVIDED. |
| | |
| | CODE REQUIREMENTS CANNOT BE DETERMINED AT THIS TIME DUE |
| | TO INSUFFICIENT INFORMATION. |
| | |
| | 2. THIS WAS SUBMITTED AS "489 EXEMPT". UNTIL IT IS |
| | DETERMINED THAT NO WORK WILL BE REQUIRED, THE PERMIT |
| | WILL NOT BE ISSUED AS 489 EXEMPT AND LICENSED |
| | CONTRACTORS WILL BE REQUIRED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 3. AN IMPACT FEE ASSESSMENT MAY BE REQUIRED (AND |
| | BUILDING PERMIT TYPE CHANGED FROM "ZONING" TO |
| | "BLD-COM"). |
| | |
| | |
| | |
| | |
| | |
| | |