| Plan Review Notes For Permit 18101364 |
| Permit Number |
18101364 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-20 03:32:56 | 1) THE FLOOR PLAN LAYOUT ON SHT. LS-101 DOES NOT MATCH | | | THE FLOOR PLAN LAYOUT ON SHT. ID-101. ALTHOUGH THE | | | SHADED AREA IS NOT IN THE SCOPE OF WORK, THE | | | CONFIGURATION/LAYOUT OF TENANT SPACE #2 ON SHEET ID-101 | | | SHOWS PARTITIONS, CORRIDORS, DOORS AND WHAT APPEARS TO | | | BE SINK YET SHEET LS-101 SHOWS NONE OF THIS. CLARIFY. | | | 2ND REQUEST. | | | 2) THE PLANS SHALL BEAR THE DIGITAL SIGNATURE AND SEAL | | | OF THE DESIGN PROFESSIONAL WHO CREATED THE PLANS. FL. | | | ADMIN. CODE RULE 61G1-16.005. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|