| 2018-11-02 09:43:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET G 004 - UNDER SECTION210000 FIRE SUPRRESSION |
| | THERE IS AN INDICATING TO REFER TO BUILDING FIRE |
| | PROTECTION DRAWINGS. |
| | |
| | THERE ARE NO FIRE PROTECTION DRAWINGS SUBMITTED. |
| | |
| | PLEASE REVIEW, CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 2) SHEET LS 101 - THERE ARE SHADED INDICATIONS THAT THE |
| | KITCHEN AREA IS NOT IN THE SCOPE OF WORK. HOWEVER, |
| | SHEET ID 109 CLEARLY SHOWS WORK IN THE KITCHEN AREA. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) THERE ARE NO INDCATIONS OF COMPLIANCE WITH THE |
| | CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE OR |
| | OTHER CURRENT EDITIONS OF APPLICABLE CODES. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE |
| | |
| | |
| | |
| | 4) THE FIRE ALARM AND FIRE SPRINKLERS SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD. |
| | |
| | ALL WORK ON THE FA AND FS SHALL BE DONE UNDER SEPRATE |
| | SHOP DRAWING PERMITS BY CERTIFIED CONTRACTORS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE |
| | NOTE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |