| Notes |
| Date |
Text |
| 2018-11-29 09:20:10 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SEE RED-LINED NOTES ON INSTALLATION SCHEDULE. USE | | | SMALLEST EFFECTIVE AREA FOR THE OPENING DESIGN | | | PRESSURES CALCULATIONS. | | | | | | 2- USE CONCRETE BLOCK ANCHOR SCHEDULE FOR SILL ANCHORS | | | UNLESS CONTRACTOR PROVES POURED CONCRETE. | | | 8" SPACING A SHOWN ON INSTALLATION SCHEDULE IS OK FOR | | | CONCRETE BLOCK INSTALLATION BASED ON THE REDUCTION | | | REQUIRED BY THE EDGE DISTANCE SPECIFIED. | | | (SEE EDGE DISTANCE VERSUS SPACING SCHEDULE FOR ANCHORS | | | TABLE ON SHEET 13 OF 20 OF SHUTTERS DRAWINGS). |
|