| 2018-11-05 14:42:02 | RESIDENTIAL (R2) FLOORING, SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | 1- THE COPIES OF THE TESTS YOU SUBMITTED ARE THE KIND |
| | OF INFORMATION WE NEED. THE ONLY THING IS THAT WE NEED |
| | COPIES OF THE TESTS DONE FOR WOOD FLOORING. THE TESTS |
| | SUBMITTED ARE FOR PORCELAIN TILE. |
| | ALSO, WE NEED THE COPY OF THE FLAME SPREAD TEST FOR |
| | FLOORING ASSEMBLY WITH WOOD FINISH AS PER YOUR PROPOSED |
| | INSTALLATION. SEE ORIGINAL COMMENTS BELOW: |
| | |
| | |
| | |
| | |
| | |
| | FLOORING UNDERLAYMENT |
| | 1- SOUND INSULATION MATERIAL SUBMITTED: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| | (2017). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND |
| | PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR |
| | 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING. |
| | TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS |
| | IN THESE BUILDINGS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |