| Permit Number |
18101285 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-29 13:47:36 | PERMIT # 18101285 | | | FIRE REVIEW | | | | | | APPROVED WITH COMMENTS: | | | | | | 1) THE OCCUPANT LOAD FOR THESE LARGE TENTS SHALL COMPLY | | | WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: | | | CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY | | | USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15 | | | SQ FT/PERSON. | | | | | | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 5)POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 6) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE | | | CANOPY MATERIAL. | | | | | | 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER | | | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 | | | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | | ENCLOSURE. | | | | | | 8) A FIRE INSPECTION AND WALK THROUGH WILL BE | | | CONDUCTED. | | | | | | |
|