Plan Review Notes
Plan Review Notes For Permit 18101272
Permit Number 18101272
Review Stop M
Sequence Number 2
Notes
Date Text
2019-01-03 12:03:48MECHANICAL PROVISOS:
 REVISION #18101272
 MASTER #15111020
 UNIT 18B
  
 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS
 AND RETURN AIR CLOSETS.
  
 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS.
  
 3) DRYER EXHAUST DUCTS SHALL NOT RUN THROUGH PLENUMS.
  
 4) MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES, KITCHEN HOOD AND EXHAUST DUCT, AND DRYER
 SHALL BE ONSITE AT TIME OF INSPECTION.
 A) ELECTRIC COOKING APPLIANCES AND EXHAUST HOODS SHALL
 BE UL LISTED AND LABELED FOR DOMESTIC USE.
 B) GAS-FIRED COOKING APPLIANCES SHALL BE LISTED AND
 LABELED FOR DOMESTIC USE AND SHALL BE TESTED IN
 ACCORDANCE WITH ANSI Z21.1, Z21.58 OR Z83.11.
  
 5) 505.2 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CFM (0.19 M3/S) SHALL BE PROVIDED WITH MAKEUP AIR
 AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE.
 SUCH MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH A MEANS
 OF CLOSURE AND SHALL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST
 SYSTEM.
  