2018-11-21 08:33:021ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18101272
 11/21/18
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BECASUE OF THE SHARED RETURN PLENUM EXCEEDING 2000
 CFMS, SMOKE DETECTORS ARE REQUIRED IN BOTH THE SUPPLY
 AND RETURN SYSTEMS- SECTION 606.2.2 FBC M. PLEASE
 PROVIDE SYMBOLS ON THE PLANS TO SHOW THE LOCATIONS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES
 DRYER- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  