| Plan Review Notes For Permit 18101269 |
| Permit Number |
18101269 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-30 18:29:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, REVISE PLAN TO INCLUDE ROOF SLOPE FOR EACH | | | SECTION OF ROOF AREA. THERE IS A PORTION WHICH APPEARS | | | TO BE FLAT; REVISE PLAN TO NOTE AREAS EXCLUDED FROM | | | THIS PERMIT. ALSO REVISE PLAN TO NOTE WHETHER ONE OR | | | TWO LAYERS OF UNDERLAYMENT ARE PROPOSED (2 LAYERS | | | REQUIRED UNDER 4/12). THIS APPEARS TO REQUIRE TWO | | | LAYERS. | | | | | | |
|