| 2018-10-26 18:15:40 | REVISION BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PRODUCT APPROVAL SUBMITTED DOESN'T INCLUDE |
| | INSTALLATION TO METAL FRAME AS SPECIFIED ON PLANS BY |
| | THE ENGINEER OF RECORD. PROVIDE PRODUCT APPROVAL THAT |
| | INCLUDES INSTALLATION AS SHOWN ON-PLANS OR REVISE PLANS |
| | TO PROVIDE SUPPORTING FRAME AS SHOWN ON THE PRODUCT |
| | APPROVAL. |
| | FAC 61G20-3.001 AND SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | REMAINDER: |
| | PLANS WERE APPROVED WITH PROVISO (SEE BELOW). THIS |
| | INFORMATION NEED TO BE PROVIDE PRIOR TO INSPECTIONS TO |
| | AVOID CONFLICTS/DELAYS. |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOOR. NOTE: PRODUCT APPROVAL TO INCLUDE |
| | INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON |
| | PLANS. |
| | B) SLIDING WINDOW. NOTE: PRODUCT APPROVAL TO INCLUDE |
| | INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON |
| | PLANS. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |