Plan Review Notes For Permit 18101195
Permit Number 18101195
Review Stop M
Sequence Number 2
Notes
Date Text
2019-01-22 12:32:002ND REVIEW FBC-2010 MECHANICAL
 PERMIT #18101195
 12/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REQUIRED DUCT SMOKE DETECTORS IN THE SUPPLY
 SYSTEMS NOT SHOWN- SEE SECTION 606.2.2 FBC M AND 1ST
 REVIEW COMMENT #5) SHEET M2.2-9D: BECAUSE OF THE SHARED
 RETURN PLENUM EXCEEDING 2000 CFMS, SMOKE DETECTORS ARE
 REQUIRED IN BOTH THE SUPPLY AND RETURN SYSTEMS OF THE
 NEW HEAT PUMPS- SECTION 606.2.2 FBC M. PLEASE PROVIDE
 SYMBOLS ON THE PLANS TO SHOW THE LOCATIONS.
  
 2) THE SUBMITTED SPECS FOR THE MIELE APPLIANCES DO NOT
 PROVIDE ANY LISTING AND LABELING DOCUMENTATION- SEE
 SECTIONS 917.1 AND 917.2 FBC M AND 1ST REVIEW COMMENT
 #6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 KITCHEN EXHAUST HOOD, COOKING APPLIANCES, AND THE
 CLOTHES DRYER- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER