| 2018-12-06 17:36:02 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | 1. THIS PROJECT IS ALL DIGITAL WHEN YOU RESUBMIT IT |
| | SHALL BE A DIGITAL RESUBMITAL. |
| | 2. PLEASE INDICATE ON THE PLAN WHAT DOCUMENT WAS USED |
| | TO COMPLY WITH FHA. |
| | 3. SHOW CLEAR FLOOR SPACE FOR KITCHEN TO COMPLY WITH |
| | FHA REQUIREMENT #7 |
| | 4. 40" CLEARANCE SHALL BE MAINTAINED AROUND THE ISLAND |
| | IN THE KITCHEN FHA REQUIREMENT #7 |
| | 5. PROVIDE NOT E OR DETAIL WITH THE HEIGHT AND WIDTH OF |
| | THE LAVATORY VANITY. FHA REQUIREMENT #7 |
| | 6. THE KNEE WALL NEXT TO TOILET SHALL BE A MAX OF 24" |
| | FHA REQUIREMENT #7 |
| | 7. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS SHOW |
| | LOCATION AND A DETAIL WITH HEIGHT DIMENSIONS FHA |
| | REQUIREMENT #6 |
| | 8. PLEASE PROVIDE ISOMETRIC DRAWING FOR SANITARY, WATER |
| | AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |