Plan Review Notes
Plan Review Notes For Permit 18101195
Permit Number 18101195
Review Stop P
Sequence Number 1
Notes
Date Text
2018-12-06 17:36:021ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
 1. THIS PROJECT IS ALL DIGITAL WHEN YOU RESUBMIT IT
 SHALL BE A DIGITAL RESUBMITAL.
 2. PLEASE INDICATE ON THE PLAN WHAT DOCUMENT WAS USED
 TO COMPLY WITH FHA.
 3. SHOW CLEAR FLOOR SPACE FOR KITCHEN TO COMPLY WITH
 FHA REQUIREMENT #7
 4. 40" CLEARANCE SHALL BE MAINTAINED AROUND THE ISLAND
 IN THE KITCHEN FHA REQUIREMENT #7
 5. PROVIDE NOT E OR DETAIL WITH THE HEIGHT AND WIDTH OF
 THE LAVATORY VANITY. FHA REQUIREMENT #7
 6. THE KNEE WALL NEXT TO TOILET SHALL BE A MAX OF 24"
 FHA REQUIREMENT #7
 7. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS SHOW
 LOCATION AND A DETAIL WITH HEIGHT DIMENSIONS FHA
 REQUIREMENT #6
 8. PLEASE PROVIDE ISOMETRIC DRAWING FOR SANITARY, WATER
 AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  