| 2018-12-03 09:51:06 | 1ST REVIEW FBC-2010 MECHANICAL |
| | PERMIT #18101195 |
| | 12/3/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW HEAT PUMP SYSTEMS- SECTION 503.2.1 FBC ENERGY |
| | CONSERVATION. |
| | |
| | 2) PROVIDE REVISED ENERGY CALCULATIONS FOR THE PROPOSED |
| | TENANT BUILDOUT- SECTION 103.2.1.2 FBC ENERGY |
| | CONSERVATION. |
| | |
| | 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-10 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 4) SHEET M2.2-9D: INDICATE HOW OUTDOOR AIR IS BEING |
| | PROVIDED TO THE APARTMENT- SECTION 401.2- FBC M. |
| | |
| | 5) SHEET M2.2-9D: BECAUSE OF THE SHARED RETURN PLENUM |
| | EXCEEDING 2000 CFMS, SMOKE DETECTORS ARE REQUIRED IN |
| | BOTH THE SUPPLY AND RETURN SYSTEMS OF THE NEW HEAT |
| | PUMPS- SECTION 606.2.2 FBC M. PLEASE PROVIDE SYMBOLS ON |
| | THE PLANS TO SHOW THE LOCATIONS. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN |
| | EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES |
| | DRYER- SECTION 304.1 FBC M. |
| | |
| | 7) M2.2-9D: THE PLAN SHOWS DUCTWORK IN THE MAIN |
| | BUILDING CORE. CLARIFY IF THIS IS NEW OR EXISTING |
| | DUCTWORK BY SHADING THE AREA OR PLACING NOTES ON THE |
| | PLAN. OTHERWISE IT WILL BE ASSUMED TO BE NEW OR ALTERED |
| | DUCTWORK THAT IS SUBJECT TO REVIEW AND INSPECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |