2018-12-03 09:51:061ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18101195
 12/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMP SYSTEMS- SECTION 503.2.1 FBC ENERGY
 CONSERVATION.
  
 2) PROVIDE REVISED ENERGY CALCULATIONS FOR THE PROPOSED
 TENANT BUILDOUT- SECTION 103.2.1.2 FBC ENERGY
 CONSERVATION.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-10 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 4) SHEET M2.2-9D: INDICATE HOW OUTDOOR AIR IS BEING
 PROVIDED TO THE APARTMENT- SECTION 401.2- FBC M.
  
 5) SHEET M2.2-9D: BECAUSE OF THE SHARED RETURN PLENUM
 EXCEEDING 2000 CFMS, SMOKE DETECTORS ARE REQUIRED IN
 BOTH THE SUPPLY AND RETURN SYSTEMS OF THE NEW HEAT
 PUMPS- SECTION 606.2.2 FBC M. PLEASE PROVIDE SYMBOLS ON
 THE PLANS TO SHOW THE LOCATIONS.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES
 DRYER- SECTION 304.1 FBC M.
  
 7) M2.2-9D: THE PLAN SHOWS DUCTWORK IN THE MAIN
 BUILDING CORE. CLARIFY IF THIS IS NEW OR EXISTING
 DUCTWORK BY SHADING THE AREA OR PLACING NOTES ON THE
 PLAN. OTHERWISE IT WILL BE ASSUMED TO BE NEW OR ALTERED
 DUCTWORK THAT IS SUBJECT TO REVIEW AND INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  