| Plan Review Notes For Permit 18101195 |
| Permit Number |
18101195 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-29 13:53:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET FA 2.2 - ALL FIRE ALARM EQUIPMENT INSTALLATION | | | SHALL BE UNDER SEPARATE SHOP DRAWINGS SUBMITTAL, BY A | | | LICENSED FA CONTRACTOR. | | | | | | PLEASE ENSURE THAT SHOP DRAWINGS ARE SUBMITTED FOR | | | APPROVAL. | | | | | | | | | | | | 2) SHEET FP 2.2 - THERE APPEARS TO BE TWO FIRE | | | SPRINKLER HEAD MISSING FROM THE PROPOSED. ONE IN THE | | | MASTER HALL AND THE OTHER IN THE AV CLOSET. | | | | | | IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS PROVISO | | | IS BEING MADE SO THAT SHOP DRAWINGS CAN BE DEVELOPED TO | | | ENSURE FIRE SPRINKLER COVERAGE IN THESE AREAS. | | | | | | PLEASE REVIEW AND CORRECT WITH SHOP DRAWINGS OR JUSTIFY | | | WITH SPECIFIC FIRE SPRINKLER CODE REFERENCES. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|