Plan Review Notes
Plan Review Notes For Permit 18101195
Permit Number 18101195
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-29 13:53:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET FA 2.2 - ALL FIRE ALARM EQUIPMENT INSTALLATION
 SHALL BE UNDER SEPARATE SHOP DRAWINGS SUBMITTAL, BY A
 LICENSED FA CONTRACTOR.
  
 PLEASE ENSURE THAT SHOP DRAWINGS ARE SUBMITTED FOR
 APPROVAL.
  
  
  
 2) SHEET FP 2.2 - THERE APPEARS TO BE TWO FIRE
 SPRINKLER HEAD MISSING FROM THE PROPOSED. ONE IN THE
 MASTER HALL AND THE OTHER IN THE AV CLOSET.
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS PROVISO
 IS BEING MADE SO THAT SHOP DRAWINGS CAN BE DEVELOPED TO
 ENSURE FIRE SPRINKLER COVERAGE IN THESE AREAS.
  
 PLEASE REVIEW AND CORRECT WITH SHOP DRAWINGS OR JUSTIFY
 WITH SPECIFIC FIRE SPRINKLER CODE REFERENCES.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  