Plan Review Notes
Plan Review Notes For Permit 18101173
Permit Number 18101173
Review Stop P
Sequence Number 1
Notes
Date Text
2018-12-28 15:57:411ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. AD1.1 THE DEMOLITION PLAN IS SHOWING A HANDICAP
 ACCESSIBLE TOILET STALL IN EACH BATHROOM THE NEW PLAN
 SHOWS TWO STANDARD TOILET STALLS IN THE SAME LOCATION
 THE LEVEL OF ACCESSIBILITY CANNOT BE REDUCED, YOU SHALL
 NOT DEMOLISH 4 ACCESSIBLE STALLS AND REPLACE THEM WITH
 2 UNISEX, SEPARATE ACCESSIBLE FACILITIES ARE REQUIRED.
 PER FBC ACC 202.3.1 AND FBC PL 403.2
  
 2. PLEASE PROVIDE DETAILS WITH THE HEIGHT DIMENSIONS
 AND CLEAR FLOOR SPACE FOR THE ACCESSIBLE BATHROOM
 FIXTURES SHALL COMPLY WITH FBC ACC 604.2, 604.3.1,
 604.4, 604.5.1, 604.5.2, 604.7, 603, 606 AND 609.4
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  