| 2018-12-10 15:05:59 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18101134 |
| | REVIEWED: DECEMBER 10, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. COVER SHEET STATES THE USE AS MERCHANTILE. |
| | [FBC 304] LISTS CARWASH AS BUSINESS GROUP. |
| | PLEASE BASE OCCUPANCY AND LOAD CALCULATIONS ON |
| | BUSINESS. |
| | |
| | 2. SHEET SP-2 SHOWS THREE NEW CONCRETE PADS AT EACH NEW |
| | DOOR. SHEET A-1 SHOWS PADS ON NEW STORE ONLY. IS THERE |
| | A PAD AT THE ADA RESTROOM? UPDATE TO MATCH. |
| | HOW ARE THESE TWO NEW AREAS ACCESIBLE WITH PROPOSED |
| | STEP FROM LANDINGS OF 5.5 INCHES? |
| | [FBC A402.1]PROVIDE ACCESSIBLE ROUTE FROM PARKING LOT |
| | (BOTH NEW AREAS) |
| | |
| | 3. [FBC 107.3.5]SHEET A-4 SHOW DETAILS 3/A4 AND 4/A4 |
| | SHOW EXISTING CEILING ABV. NEW FRAMED CEILING. SHEET |
| | A-1 SAYS DROP CEILING. PLEASE CLARIFY WHAT IS EXISTING |
| | STRUCTURE THAT NEW WALLS ARE CONNECTING TO, WHAT TYPE |
| | OF CEILING IS IT AND CONNECTORS BEING USED TO CONNECT |
| | TO EXISTING? |
| | |
| | 4. [FBC ENERGY C401.2]ENERGY COOLING CALCULATIONS WERE |
| | MADE FOR 350 SQ. FT. THE NEW A/C AREA IS 280 ACCORDING |
| | TO COVER SHEET. PLEASE ADJUST ENERGY CALCULATIONS FOR |
| | AREA WITH A/C AT 280. |
| | |
| | 5. [FL.STATUTE 553.842]PRODUCT APPROVAL FOR STOREFRONT |
| | SYSTEM IS EXPIRED. |
| | PLEASE PROVIDE UPDATED VERSION FOR NOA 16-0208.13. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |