2019-01-19 10:45:43****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE PENDING ITEMS FROM LAST REVIEW CONTINUE AS NOTED
 BELOW:
  
 1. VALUATION: THE VALUATION SHOWN ON THE APPLICATION
 SHOULD BE A TOTAL AND NEEDS TO INCLUDE VALUE OF RELATED
 SUB PERMITS.
  
 2. THE TIE BEAM DIMENSIONS ARE NOT INCLUDED ON THE
 LATEST SUBMITTED PLAN. ON THE INITIAL PLAN SUBMITTAL AN
 8" X 12" TIE BEAM WAS SHOWN BUT THERE WAS ALSO A DETAIL
 FOR AN 8" X 8" BOND BEAM. PLEASE CLARIFY.
  
 3. THE WINDOW SCHEDULE IDENTIFICATION "MARKS" DO NOT
 MATCH THE IDENTIFACATION NUMBERS SHOWN ON THE OPENINGS
 OF THE FLOOR PLAN.
  
 4. PLEASE PROVIDE A CONNECTOR SCHEDULE FOR THE ROOF
 TRUSS TO THE TIE BEAM. THE SCHEDULE NEEDS TO INCLUDE
 THE SPECIFIC CONNECTORS TO BE USED AND NUMBER/SIZE OF
 FASTENERS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.