| Plan Review Notes For Permit 18101088 |
| Permit Number |
18101088 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-12-20 14:52:33 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | 1. THE VALUATION OF THIS JOB APPEARS TO BE VERY LOW, AS | | | THE PLANS INCLUDE: | | | BUILDING: | | | BLOCK WALL(APPROX. 50') TO BE REPLACED. | | | ROOF & FLOOR FRAMING MEMBERS TO BE REPAIRED/REPLACED | | | (INCLUDING SHEATHING). | | | WINDOW/DOOR REPLACEMENT (IMPACT RESISTANT). | | | INTERIOR WALL & DOOR FRAMING TO BE REMOVED/REPLACED. | | | ELECTRIC: AS SHOWN ON PLANS (NO SUB-PERMIT). | | | PLUMBING: AS SHOWN ON PLANS (NO SUB-PERMIT). | | | | | | 2. THE BUILDING PLANS (PAGE A-2) ARE MISSING THE | | | DIMENSIONS OF THE FOOTINGS AND TIE-BEAMS. | | | | | | 3. THERE IS NO SCHEDULE FOR WINDOWS AND DOORS. | | | | | | NOTES: | | | | | | THERE WERE NO PRODUCT APPROVALS (WINDOWS/DOORS AND | | | ROOFING PRODUCTS) SUBMITTED WITH PLANS. | | | THERE IS A DEMO PERMIT THAT IS STILL OPEN. | | | THERE HAVE BEEN NO OTHER PERMITS APPLIED FOR (SUCH AS | | | MECHANICAL AND ROOFING). | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|