| Notes |
| Date |
Text |
| 2019-02-05 14:54:30 | | | | APPROVED | | | PLUMBING PROVISO | | | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S | | | APPROVAL | | | 2. WASHER AND SINK SHALL CONNECT DOWNSTREAM OF BATHROOM | | | PER FBC PL 912.1 AND FBC RES P3108.1 | | | 3. PROVIDE THERMAL EXPANSION CONTROL DEVICE FOR COLD | | | WATER SUPPLY TO TANK TYPE WATER HEATER PER FBC PL 607.3 | | | AND FBC RES P2903.4.2 | | | 4. T & P RELIEF LINE SHALL DISCHARGE THROUGH AN AIR GAP | | | IN THE SAME ROOM AS THE WATER HEATER PER FBC PL 504.6 | | | (2) AND FBC RES P2804.6.1 (2) | | | 5. T & P RELIEF LINE SHALL DISCHARGE TO A POINT THAT IS | | | READILY OBSEVABLE TO THE BUILDING OCCUPANTS PER FBC PL | | | 504.6 (7) AND FBC RES P2804.6.1 (7) | | | 6. T & P RELIEF LINE SHALL NOT BE TRAPPED PER FBC PL | | | 504.6 (8) AND FBC RES P2804.6.1 (8) | | | |
|