Plan Review Notes
Plan Review Notes For Permit 18101088
Permit Number 18101088
Review Stop P
Sequence Number 2
Notes
Date Text
2019-02-05 14:54:30 
 APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL
 2. WASHER AND SINK SHALL CONNECT DOWNSTREAM OF BATHROOM
 PER FBC PL 912.1 AND FBC RES P3108.1
 3. PROVIDE THERMAL EXPANSION CONTROL DEVICE FOR COLD
 WATER SUPPLY TO TANK TYPE WATER HEATER PER FBC PL 607.3
 AND FBC RES P2903.4.2
 4. T & P RELIEF LINE SHALL DISCHARGE THROUGH AN AIR GAP
 IN THE SAME ROOM AS THE WATER HEATER PER FBC PL 504.6
 (2) AND FBC RES P2804.6.1 (2)
 5. T & P RELIEF LINE SHALL DISCHARGE TO A POINT THAT IS
 READILY OBSEVABLE TO THE BUILDING OCCUPANTS PER FBC PL
 504.6 (7) AND FBC RES P2804.6.1 (7)
 6. T & P RELIEF LINE SHALL NOT BE TRAPPED PER FBC PL
 504.6 (8) AND FBC RES P2804.6.1 (8)
  