| 2019-01-23 15:20:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. THE DRYER AND LAUNDRY LOAD IS NOT |
| | INCLUDED, THE VALUE FOR THE RANGE IS NOT CODE |
| | COMPLIANT, AND THERE IS CONFUSION ON THE HVAC SYSTEM - |
| | PROVIDE CLARIFICATION. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 3. PROVIDE CLARIFICATION FOR HVAC. THE PANEL SCHEDULE |
| | SHOWS 5 DIFFERENT UNITS, BUT THE LOAD CALCULATION |
| | INCLUDES ONE CALCULATION FOR HEAT AT 65% DEMAND FACTOR, |
| | WHICH IS TYPICALLY USED FOR ONE CENTRAL SYSTEM. WHICH |
| | IS IT? LOAD CALCULATION SHOULD INCLUDE THE LARGER OF |
| | THE AC OR HEAT LOADS, BUT NOT BOTH.WPB FBC 107.2.1; NEC |
| | 220; FBC RE E3602.2 |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 5. PROVIDE LOCATION OF ELECTRICAL PANEL AND SERVICE ON |
| | PLAN. WPB FBC 107.2.1 |
| | 6. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9; FBC RE E3606.3 |
| | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 8. CORRECT SYMBOLS ON PLAN TO MATCH LEGEND FOR SMOKE |
| | ALARMS. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |