| Plan Review Notes For Permit 18101088 |
| Permit Number |
18101088 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-29 17:09:38 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | THE EXISTING STRUCTURE DOES NOT APPEAR TO MATCH THE | | | DESCRIBED STRUCTURE ON PLANS. THE EXISTING STRUCTURE | | | APPEARS TO BE TWO STRUCTURES JOINED TOGETHER WITH THE | | | EAST HALF HAVING A SLOPED ROOF, A FRONT PORCH, & | | | SEVERAL WINDOWS. PLEASE PROVIDE MORE DETAILS ON PLAN | | | INCLUDING: | | | | | | 1. FBC EC R503.1.1 LOCATION AND SIZE OF WINDOW/DOOR | | | OPENINGS. | | | 2. FBC EC R503.1.1.1 PROVIDE REPLACEMENT FENESTRATION | | | DETAILS INCLUDING PRODUCT APPROVALS FOR NEW WINDOWS AND | | | DOORS. | | | 3. FBC EB 807.2 CONNECTION DETAILS FOR THE NEW WALL TO | | | EXISTING WALLS. | | | 4. FBC EB 807.2 DETAILS FOR THE ATTACHMENT OF | | | REPLACEMENT JOISTS. | | | 5. FBC EB 807.2 DETAILS FOR THE TIE DOWN ATTACHMENTS OF | | | NEW WALL TO EXISTING ROOF. | | | 6. FBC EB 807.2 DETAILS FOR THE NEW BLOCK WALL FOOTING. | | | (NOTES ON PLAN DO NOT MATCH/PROVIDE FOOTING DETAIL) | | | 7. FBC R 702. DETAILS FOR THE INTERIOR FRAMING: FURRING | | | & INSULATION OF NEW WALL. | | | 8. FBC EB 808.3 PROVIDE AN ELECTRIC SUB PERMIT. | | | |
|