2019-12-17 13:01:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 12/17/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.04: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 FLAMEBAR HAZARDOUS EXHAUST DUCT.THE SPECS SHALL SHOW
 HOW THE DUCT IS TO BE ASSEMBLED, SUPPORTED, AND
 FIRESTOPPED AT RATED WALL PENETRATIONS- SECTION 107.2.1
 WPB AND SECTION 510.9 FBC M.
  
 2) M2.04: SEE NOTE #8 AND SUBMIT TWO COPIES OF PLAN
 SHEET M7.03 SHOWING THE EXHAUST THIMBLE PENETRATION
 DETAIL- SECTION 107.2.1 WPB.
  
 3) M2.04: PROVIDE THE SEQUENCE OF OPERATION FOR EXHAUST
 FANS GEF-4.5 & GEF-4.6- SECTION 510.2 FBC M.
  
 4) M2.04: PROVIDE A MIAMI-DADE NOA OR FL. PRODUCT
 APPROVAL FOR THE RUSHKIN LOUVERS- RULE 9N-3 FAC. NOTE:
 THE LOUVERS MAY BE A DEFFERRED SUBMITTAL IF REQUESTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  