| 2019-12-17 13:01:32 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18101052 |
| | 12/17/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.04: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | FLAMEBAR HAZARDOUS EXHAUST DUCT.THE SPECS SHALL SHOW |
| | HOW THE DUCT IS TO BE ASSEMBLED, SUPPORTED, AND |
| | FIRESTOPPED AT RATED WALL PENETRATIONS- SECTION 107.2.1 |
| | WPB AND SECTION 510.9 FBC M. |
| | |
| | 2) M2.04: SEE NOTE #8 AND SUBMIT TWO COPIES OF PLAN |
| | SHEET M7.03 SHOWING THE EXHAUST THIMBLE PENETRATION |
| | DETAIL- SECTION 107.2.1 WPB. |
| | |
| | 3) M2.04: PROVIDE THE SEQUENCE OF OPERATION FOR EXHAUST |
| | FANS GEF-4.5 & GEF-4.6- SECTION 510.2 FBC M. |
| | |
| | 4) M2.04: PROVIDE A MIAMI-DADE NOA OR FL. PRODUCT |
| | APPROVAL FOR THE RUSHKIN LOUVERS- RULE 9N-3 FAC. NOTE: |
| | THE LOUVERS MAY BE A DEFFERRED SUBMITTAL IF REQUESTED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |