2019-11-27 13:04:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 11/27/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.04: THE GENERATOR WAS NOT REVIEWED UNDER
 THE MAIN PERMIT PLAN REVISIONS. REVIEW OF THE SHEET
 INDICATES THESE ISSUES:
  
 A) THE HAZARDOUS EXHAUST DUCT FROM THE TANK ROOM SHALL
 RUN INDEPENDENTLY FROM THE TANK ROOM TO THE EXTERIOR OF
 THE BUILDING. IT IS NOT PERMITTED TO BE CONNECTED TO
 THE GENERATOR RADIATOR EXHAUST- SECTIONS 510.2 &
 510.6.7 FBC M.
  
 B) THE FIRE DAMPER AT THE HAZARDOUS EXHAUST DUCT
 PENETRATION OF THE FIRE-RATED TANK/GENERATOR ROOM WALL
 IS NOT ALLOWED- SECTION 510.7.1 FBC M. THE DUCT SHALL
 BE PROTECTED WITH A FIRE-RATED ENCLOSURE FROM THE POINT
 OF PENETRATION OF THE RATED WALL TO THE DISCHARGE
 OUTLET AT THE EXTERIOR WALL- SECTION 510.7.3 FBC M.
  
 2) SUBMIT A CORRECTED M2.04 PLAN SHEET AND ORGANIZE ALL
 PLAN SHEETS INTO TWO COMPLETE COLLATED SETS FOR REVIEW-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  