Plan Review Notes
Plan Review Notes For Permit 18101052
Permit Number 18101052
Review Stop E
Sequence Number 2
Notes
Date Text
2019-11-22 17:21:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE HAS BEEN ADDRESSED.
  
 2) RISER DIAGRAM SHOWING WIRE SIZES AND DISCONNECT
 SIZES OCP SIZES.
  
 3) THE DRAWINGS THAT ARE HERE IONLY HAVE ONE SET OF
 INCOMPLETE PLANS, PLEASE ORGANIZE THE DRAWINGS FOR
 ELECTRICAL INTO ONE SET SO I DON'T HAVE TO GO THROUGH
 ALL THE DRAWINGS TO FIND THE ELECTRICAL ONES.
  
  
  
  