| Notes |
| Date |
Text |
| 2019-11-22 17:21:51 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE HAS BEEN ADDRESSED. | | | | | | 2) RISER DIAGRAM SHOWING WIRE SIZES AND DISCONNECT | | | SIZES OCP SIZES. | | | | | | 3) THE DRAWINGS THAT ARE HERE IONLY HAVE ONE SET OF | | | INCOMPLETE PLANS, PLEASE ORGANIZE THE DRAWINGS FOR | | | ELECTRICAL INTO ONE SET SO I DON'T HAVE TO GO THROUGH | | | ALL THE DRAWINGS TO FIND THE ELECTRICAL ONES. | | | | | | | | | | | | |
|