| Date |
Text |
| 2018-12-06 09:15:29 | 1) THE GENERATOR SPECIFICATIONS NOTE THAT THE GENERATOR |
| | OFFERS A UL 2200 LISTING. SUBMIT A COPY OF THE |
| | CERTIFICATE OF COMPLIANCE SHOWING THE UL 2200 LISTING. |
| | 2017 FBC-MECH. SEC.915. |
| | 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA 37 |
| | PER 2017 FBC-MECH. SEC. 915. I COULD NOT FIND THIS |
| | INFORMATION IN THE SPECIFICATIONS. |
| | 3) THE FUEL TANK INSTALLATION SHALL BE APPROVED BY THE |
| | PALM BEACH COUNTY OFFICE OF ENVIRONMENTAL RESOURCE |
| | MANAGEMENT PER PALM BEACH COUNTY ORDINANCE 2015-008. |
| | SUBMIT DOCUMENTATION FROM ERM THAT THIS INSTALLATION |
| | HAS BEEN APPROVED. |
| | 4) THE SUBMITTED PLANS SHALL BEAR THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE |
| | WITH THE FL. ADMIN. CODE RULE 61G15-23.001. |
| | 5) SUBMIT SAFETY DATA SHEETS FOR THE FUEL OIL TO BE |
| | USED. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) INDICATE THE CLASS OF THE FUEL ON THE PLANS IN |
| | ACCORDANCE WITH NFPA 30 SEC. 4.3. |
| | 7) SPILL CONTROL, CONTAINMENT AND DRAINAGE MAY BE |
| | REQUIRED FOR THE FUEL TANK DEPENDING ON THE CLASS OF |
| | LIQUID OF THE FUEL. NFPA 30 SEC. 9.13. |
| | 8) IN ADDITION TO THE TANK PLANS THAT HAVE BEEN |
| | SUBMITTED, SUPPLY ANY ADDITIONAL MANUFACTURER'S |
| | SPECIFICATIONS FOR THE FUEL TANK.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 9) THE SUBMITTED TANK PLANS NOTE THE TANK AS 660 |
| | GALLONS BUT THE PLANS NOTE THE TANK AS 600 GALLONS. |
| | CLARIFY. |
| | 10) THE FUEL TANK VENTS SHALL BE 5 FEET FROM BUILDING |
| | OPENINGS AND 15 FEET FROM POWERED VENTILATION AIR |
| | INTAKES PER NFPA 30-12 SEC.19.5.3.2. |
| | 11) A SIGN OR MARKING THAT MEETS THE REQUIREMENTS OF |
| | NFPA 704, OR ANOTHER APPROVED SYSTEM, SHALL BE APPLIED |
| | TO STORAGE TANKS CONTAINING LIQUIDS PER NFPA 30 |
| | SEC.21.7.2.1. |
| | 12) EMERGENCY RELIEF VENTING IS REQUIRED FOR THE FUEL |
| | TANK PER NFPA 30 SEC.22.7. |
| | 13) SHOW ON THE PLAN HOW THE VENT PIPES FROM THE FUEL |
| | TANK WILL BE PROTECTED WHERE PASSING THROUGH THE WALLS |
| | OF THE STRUCTURE. |
| | 14) THE FILL PORT FOR THE FUEL TANK SHALL BE PROVIDED |
| | ON AN EXTERIOR WALL OF THE ROOM OR STRUCTURE ENCLOSING |
| | THE TANK AT A POINT AT LEAST 24 INCHES FROM ANY |
| | BUILDING OPENING AT THE SAME OR LOWER LEVEL PER NFPA |
| | 37-15 SEC. 6.6.3.3. SHOW THE LOCATION OF THE FILL PORT |
| | ON THE PLANS. |
| | 15) THE FUEL TANK SHALL BE LOCATED IN A ROOM WITH A |
| | FIRE- RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE |
| | THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.1.2 , THE REQUIERED FIRE-RESISTANCE |
| | RATING SHALL BE REDUCED TO ONE HOUR. 2017 FBC-BUILDING |
| | SEC.403.4.8.2. |
| | 16) THE PLANS SHOW THE FUEL TANK LOCATED IN A SEPARATE |
| | ROOM THAT IS NOT SHOWN ON THE ORIGINAL PLANS. A |
| | REVISION SHALL BE SUBMITTED SHOWING THE FIRE RATING OF |
| | THE ROOM AND DOORS IN WHICH THE FUEL TANK IS LOCATED. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 17) A PLUMBING REVISION SHALL BE SUBMITTED FOR SHT. P |
| | 5.01 AS THE FUEL PIPING WAS NOT SHOWN ON THE ORIGINAL |
| | PLANS. |
| | 18) SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PRYCO FUEL DELIVERY CONTROL STATION FOR REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |