2018-12-11 13:22:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS,
 AND PROVIDE AN EXHAUST PIPE DRAWING SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND
 ANY CONTRACTOR SUPPLIED PIPING.
  
 2) PROVIDE A BACKPRESSURE CALCULATION FOR THE EXHAUST
 PIPING SYSTEM AND THE SILENCER AS RECOMMENDED BY
 KOHLER. ACCORDING TO THE KOHLER SPECIFICATIONS, THE
 CALCULATION SHALL BE PERFORMED BY AN AUTHORIZED
 DISTRIBUTOR/DEALER OF THE FLEX EXHAUST PIPING. AND
 SHALL INCLUDE THE FLEX, THE SILENCER, AND ANY
 CONTRACTOR SUPPLIED PIPING.
  
 3) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND
 THE FUEL TANK- SECTION 304.1 FBC M.
  
 4) SHEET E2.04 & E4.02: THE PLANS SHOW A SEPARATE FUEL
 TANK ROOM THAT THE APPROVED PLAN SHEET M2.04 UNDER
 PERMIT #16061443 DOES NOT SHOW. PLEASE REVISE ALL PLANS
 FROM THE APPROVED MASTER SET THAT ARE AFFECTED BY THIS
 CHANGE AND SUBMIT THEM TO THE BUILDING DEPT. FOR REVIEW
 WITH A REVISION APPLICATION.
  
 5) PROVIDE A MECHANICAL PLAN INDICATING HOW THE NEW
 TANK ROOM WILL BE VENTILATED- SECTION 415.9.1.5 FBC B,
 AND SECTION 510 FBC M.
  
 6) PROVIDE A LIST OF STANDBY AND EMERGENCY POWER LOADS
 THAT THE GENERATOR WILL POWER- SECTIONS 403.4.8.3 &
 403.4.8.4 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719