| 2018-12-11 13:22:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18101052 |
| | 12/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS, |
| | AND PROVIDE AN EXHAUST PIPE DRAWING SHOWING THE TOTAL |
| | SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL |
| | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND |
| | ANY CONTRACTOR SUPPLIED PIPING. |
| | |
| | 2) PROVIDE A BACKPRESSURE CALCULATION FOR THE EXHAUST |
| | PIPING SYSTEM AND THE SILENCER AS RECOMMENDED BY |
| | KOHLER. ACCORDING TO THE KOHLER SPECIFICATIONS, THE |
| | CALCULATION SHALL BE PERFORMED BY AN AUTHORIZED |
| | DISTRIBUTOR/DEALER OF THE FLEX EXHAUST PIPING. AND |
| | SHALL INCLUDE THE FLEX, THE SILENCER, AND ANY |
| | CONTRACTOR SUPPLIED PIPING. |
| | |
| | 3) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND |
| | THE FUEL TANK- SECTION 304.1 FBC M. |
| | |
| | 4) SHEET E2.04 & E4.02: THE PLANS SHOW A SEPARATE FUEL |
| | TANK ROOM THAT THE APPROVED PLAN SHEET M2.04 UNDER |
| | PERMIT #16061443 DOES NOT SHOW. PLEASE REVISE ALL PLANS |
| | FROM THE APPROVED MASTER SET THAT ARE AFFECTED BY THIS |
| | CHANGE AND SUBMIT THEM TO THE BUILDING DEPT. FOR REVIEW |
| | WITH A REVISION APPLICATION. |
| | |
| | 5) PROVIDE A MECHANICAL PLAN INDICATING HOW THE NEW |
| | TANK ROOM WILL BE VENTILATED- SECTION 415.9.1.5 FBC B, |
| | AND SECTION 510 FBC M. |
| | |
| | 6) PROVIDE A LIST OF STANDBY AND EMERGENCY POWER LOADS |
| | THAT THE GENERATOR WILL POWER- SECTIONS 403.4.8.3 & |
| | 403.4.8.4 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |