2018-12-14 13:43:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 THE INSTALLATION SHALL COMPLY WITH :
  
 NFPA? 37 STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES 2015
 EDITION
  
 NFPA? 110 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS 2013 EDITION
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE .
  
  
  
 2) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST OF THE
 GENERATOR IS BEING LOCATED .
  
 PLEASE REVIEW AND PROVIDE IN COMPLAINCE WITH ABOVE
 NOTED CODES.
  
  
  
  
 3) THERE ARE NO INDICATIONS OF ANY FIRE RATED LISTINGS
 FOR ANY BREECHES TO THE FIRE WALLS.
  
 PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR EACH FIRE
 WALL BREECHED BY ANY PIECE OF EQUIPMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  