| Plan Review Notes For Permit 18101052 |
| Permit Number |
18101052 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-14 13:43:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | | CODES. | | | | | | THE INSTALLATION SHALL COMPLY WITH : | | | | | | NFPA? 37 STANDARD FOR THE INSTALLATION AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES 2015 | | | EDITION | | | | | | NFPA? 110 STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS 2013 EDITION | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE . | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST OF THE | | | GENERATOR IS BEING LOCATED . | | | | | | PLEASE REVIEW AND PROVIDE IN COMPLAINCE WITH ABOVE | | | NOTED CODES. | | | | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF ANY FIRE RATED LISTINGS | | | FOR ANY BREECHES TO THE FIRE WALLS. | | | | | | PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR EACH FIRE | | | WALL BREECHED BY ANY PIECE OF EQUIPMENT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|