Plan Review Notes
Plan Review Notes For Permit 18101052
Permit Number 18101052
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-18 08:23:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS SUBMITTED FOR REVIEW FROM A DESIGN
 PROFESSIONAL SHALL BEAR THE ORIGINAL SIGNATURE AND SEAL
 OF THE DESIGN PROFESSIONAL.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2. PROVIDE SITE PLAN. IDENTIFY LOCATION OF GENERATOR
 EXHAUST.
  
 3. PROVIDE APPROVAL LETTER FROM PALM BEACH COUNTY
 ENVIROMENTAL RESOURCES MANAGEMENT FOR THE INSTALLATION
 OF THE FUEL TANK.
  
 4. TANK PLANS SUBMITTAL INDICATES A 660 GAL. FUEL TANK.
 PLAN PAGE P5.01 INDICATES A 600 GAL FUEL TANK. PLEASE
 CLARIFY.
  
 5. PROVIDE DETAIL AND/OR UL DESIGN FOR ANY PIPES
 PENETRATING A RATED WALL ASSEMBLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  