2019-06-12 10:17:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LIGHT FIXTURE SCHEDULE FOR LIGHTING IN POOL
 AND POOL AREA. SOME OF THE FIXTURES SPECIFIED ARE NOT
 ON THE ORIGINAL LIGHT FIXTURE SCHEDULE. BE ADVISED THAT
 FIXTURE RL2 IS SHOWN IN ORIGINAL LIGHT FIXTURE SCHEDULE
 AS A 277 VOLT FIXTURE. SHEET E-104 SHOWS IT BEING FED
 FROM A 120/208 VOLT PANEL. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 2. SHEET E-104 SHOWS FIXTURE RL2 LOCATED APPROXIMATELY
 54 INCHES FROM POOL. NO LIGHT FIXTURE SHALL BE
 INSTALLED LOWER THAN 12 FEET WHEN WITHIN 5 FEET OF THE
 POOL. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC
 680.22(B)(1)
 3. SHEET P2.0 SHOWS ONLY FIXTURE TYPE FL1 IN THE
 PLANTERS. SHEET E-104 SHOWS FL2 IN THE PLANTER, AND FL1
 SURROUNDING THE PLANTER. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 4. SHEET E-104 IN A BLOCK NOTE STATES THAT ALL CIRCUITS
 WITHIN 5-10 FEET OF POOL SHALL BE PROTECTED BY A GFCI
 BREAKER. THE PANEL SCHEDULES FOR THESE CIRCUITS DO NOT
 REFLECT THIS REQUIREMENT. SOME OF THE PANEL SCHEDULES
 FOR LIGHTING IN THE POOL AREA ARE NOT INCLUDED IN THIS
 SUBMISSION. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 680.22(B)(4)
 5. LIGHT FIXTURE B IS SHOWN IN SEVERAL LOCATIONS. WHAT
 ARE THESE FIXTURES? SHOW COMPLIANCE WITH FBC 454.1.4.2
 FOR MINIMUM LIGHTING LEVELS, AND NEC 680.22 OR 680.23
 AS APPLICABLE FOR VOLTAGE/GFCI PROTECTION AS REQUIRED.
 6. SHEET P2.0 QUOTES THE REQUIREMENT FOR UNDERWATER
 LIGHTING STATING THAT IT IS FROM THE 2017 FBC. THIS
 CODE SECTION QUOTED, FBC 454.1.4.2.3, IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. WPB FBC 107.2.1; FBC
 454.1.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  