| Plan Review Notes For Permit 18101050 |
| Permit Number |
18101050 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-11 15:39:56 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) NOT COMPLIED. SIGNED AND SEALED CALCULATIONS AS | | | REQUESTED WERE NOT PROVIDED. SUBMIT THE TEST REPORTS OF | | | THE FOAM FOR THE FLAME SPREAD AND SMOKE DEVELOPED (ASTM | | | E84 OR UL 723). PROVIDE DETAILS ON THE PLANS OF HOW THE | | | FOAM WILL BE ENCASED IN CONCRETE AS REQUIRED BY FBC | | | 603.1. | | | STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW THE | | | POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING THE | | | POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS FOAM | | | WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO SHOW | | | THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED POOL. | | | FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II BUILDINGS IS | | | REQUIRED TO BE ENCASED IN CONCRETE. FBC 603.1 | | | | | | NOTE: WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | | | | | | | |
|