2018-12-26 10:44:12PLAN REVIEW COMMENTS
  
 1) THE ELECTRICAL PLAN SHEET E1.0 THAT IS LISTED IN THE
 TABLE OF CONTENTS ON SHEET P1.0 WAS NOT UPLOADED. WITH
 THIS SUBMITTAL. FBC 107.2.1
 2) STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW
 THE POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING
 THE POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS
 FOAM WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO
 SHOW THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED
 POOL. FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II
 BUILDINGS IS REQUIRED TO BE ENCASED IN CONCRETE. FBC
 603.1.
 3) SHT. P2.1 - THE EQUALIZER IS SHOWN AS 2 INCH AND
 ALSO AS 4 INCH. CLARIFY.
 4) THE PLANS SHALL BE DIGITALLY SIGNED AND SEALED PER
 FL. ADMIN. CODE RULE 61G15-23.003,
 5) A VAPOR RETARDANT COVER ON OR AT THE WATER SURFACE
 OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT
 LOSS SHALL BE PROVIDED PER THE 2017 FBC-ENERGY SEC.
 C404.9.3.
 6) THE EQUIPMENT ROOM SHALL HAVE EITHER FORCED DRAFT OR
 CROSS VENTILATION PER 2017 FBC SEC. 4541.5.4. PROVIDE
 DDETAILS.
 7) SHT. P2.2 - SHOW THE SIZE AND TERMINATION POINT OF
 THE CONDENSATE DRAINS.
 8) SHT. P2.3 - TYPICAL MAIN DRAIN DETAILS CALLS OUT 3
 MAIN DRAINS BUT SHT. P2.1 SHOWS 4. CLARIFY.
 9) SHT.P2.0 - POOL MATERIALS & EQUIPMENT
 LIST/PLUMBING/EQUIPMENT ROOM REFERS TO SHT. P4.0 FOR
 COMPLETE SPECS. THERE IS NO SHT. P4.0 IN THIS
 SUBMITTAL. CLARIFY.
 10) A REDUCED PRESSURE ZONE BACKFLOW PREVENTER IS
 REQUIRED ON THE WATER SUPPLY TO THE COLLECTOR TANK PER
 CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 11) THE OPERABLE PARTS OF THE RINSE SHOWER SHALL
 CCOMPLY WITH THE 2017 FBC-ACCESS. SEC.309.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW