| 2018-11-27 14:39:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND |
| | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A |
| | DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE |
| | CORRECTION. WPB FBC 107.1; FS 471/481 |
| | 2. ON SHEET P1.0, TABLE OF CONTENTS, IT SHOWS SHEET |
| | E1.0. THIS SHEET IS NOT INCLUDED IN SUBMISSION. PROVIDE |
| | FOR REVIEW. WPB FBC 107.1, 107.2.1 |
| | 3. PROVIDE ENCLOSURE FOR ELECTRICAL PANEL THAT MEETS |
| | THE REQUIREMENTS OF NEC FOR EXPOSURE TO CORROSIVE |
| | AGENTS. NEC TABLE 110.28 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |