Plan Review Notes
Plan Review Notes For Permit 18101050
Permit Number 18101050
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-11 11:46:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS. THE ELECTRONICALLY SUBMITTED
 PLANS REQUIRE THE ENGINEER'S DIGITAL SIGNATURE. FAC
 61G15-23.003
  
 2) THE ELECTRICAL PLAN SHEET E1.0 THAT IS LISTED IN THE
 TABLE OF CONTENTS ON SHEET P1.0 WAS NOT UPLOADED. WITH
 THIS SUBMITTAL. FBC 107.2.1
  
 3) SHOW HOW COMPLIANCE WITH FBC 454.1.3.1.9 WILL BE
 MET. ALL PUBLIC POOLS SHALL BE SURROUNDED BY A MINIMUM
 48 INCH (1219 MM) HIGH FENCE OR OTHER APPROVED
 SUBSTANTIAL BARRIER. THE FENCE SHALL BE CONTINUOUS
 AROUND THE PERIMETER OF THE POOL AREA THAT IS NOT
 OTHERWISE BLOCKED OR OBSTRUCTED BY ADJACENT BUILDINGS
 OR STRUCTURES AND SHALL ADJOIN WITH ITSELF OR ABUT TO
 THE ADJACENT MEMBERS. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. DOORED ACCESS POINTS FROM PUBLIC ROOMS
 SUCH AS LOBBIES OR CLUB HOUSES NEED NOT BE THROUGH
 GATES IF THE DOOR(S) MEET THE SAME SELF-CLOSING,
 SELF-LATCHING REQUIREMENTS AS A GATE. GATES SHALL OPEN
 OUTWARD AWAY FROM THE POOL AREA. A LATCHED, LOCKABLE
 GATE SHALL BE PLACED IN THE FENCE WITHIN 10 FEET (3048
 MM) OF THE CLOSEST POINT BETWEEN THE POOL AND THE
 EQUIPMENT AREA FOR SERVICE ACCESS.
  
 4) 454.1.2.3.5 RULES AND REGULATIONS SIGNAGE. ITEM #8
 WAS NOT INCLUDED ON YOUR SIGNAGE 8.IF THE POOL INCLUDES
 A SUN SHELF, "WARNING: DROP OFF AT SUN SHELF EDGE IS
 _X_ FEET DEEP" IN 4-INCH (102 MM) LETTERS.
  
 5) STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW
 THE POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING
 THE POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS
 FOAM WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO
 SHOW THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED
 POOL. FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II
 BUILDINGS IS REQUIRED TO BE ENCASED IN CONCRETE. FBC
 603.1
  
 NOTE: WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  
  
  
  