| Plan Review Notes For Permit 18101042 |
| Permit Number |
18101042 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-25 14:26:46 | 1) THE VALUE FOR THE SCOPE OF WORK TO BE SEEMS | | | LOW.SUBMIT DETAILED DOCUMENTATION SHOWING THE VALUE OF | | | ALL WORK TO BE DONE. FBC 109.3. | | | 2) SIZE ALL THE PLUMBING LINES ON THE DRAWING INCLUDING | | | THE VENTS. FBC SEC. 107.2.1, 2017 FBCR - PLUMBING | | | SEC.P3005. | | | 3) SUBMIT AN EXISTING FLOOR PAN AND A PROPOSED FLOOR | | | PLAN. CLEARLY SHOW THE ENTIRE SCOPE OF WORK TO BE DONE. | | | 2017 FBC SEC. 107.2.1. SHOW WHAT IS EXISTING TO REMAIN | | | AND WHAT WILL BE NEW. | | | 4) SUBMIT TWO COMPLETE SETS OF PLANS FOR ALL THE WORK | | | BEING DONE. INCLUDE BUILDING, ELECTRICAL, MECHANICAL, | | | ETC. 2017 FBC SEC. 107.2.1. | | | 5) SHOW THE LENGTH AND WIDTH OF THE NEW SHOWERS. COMPLY | | | WITH 2017 FBCR SEC.P2709.1. | | | 6) SHOW THE REQUIRED FIXTURE CLEARANCES ON THE PLANS. | | | COMPLY WITH 2017 FBCR SEC.P2705.1 (5). | | | 7) CLEANOUTS ARE REQUIRED IN THE WATSE STACKS PER 2017 | | | FBCR SEC.P3005.2. | | | NOTE: A THOROUGH REVIEW COULD NOT BE DONE AS THE | | | SUBMITTED PLANS ARE VAGUE AS TO THE SCOPE OF WORK BEING | | | DONE.ADDDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON RESUBMITTAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|