| 2018-11-29 16:27:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.RE: PLAN PAGE P3; WASHING MACHINE DETAIL. |
| | A) PER FBC PL 1003.10, ACCESS SHALL BE PROVIDED TO EACH |
| | INTERCEPTOR AND SEPARATOR FOR SERVICE AND MAINTENANCE. |
| | INTERCEPTORS AND SEPARATORS SHALL BE MAINTAINED BY |
| | PERIODIC REMOVAL OF ACCUMULATED GREASE, SCUM, OIL, OR |
| | OTHER FLOATING SUBSTANCES AND SOLIDS DEPOSITED IN THE |
| | INTERCEPTOR OR SEPARATOR. THE ACCESS PANEL FOR THE LINT |
| | INTERCEPTOR BEHIND A WASHING MACHINE THAT WOULD HAVE TO |
| | BE DISCONNECTED AND MOVED TO PROVIDE ACCESS TO THE |
| | PANEL DOES NOT LEND ITSELF TO PERIODIC MAINTENANCE. |
| | ADDITIONALLY, INSTALLATION IS IN A 1HR FIRE RATED WALL. |
| | THE SIOUX CHIEF ACCESS PANEL NOTED IS NOT FIRE RATED. |
| | B) PROVIDE A UL LISTED WASHING MACHINE SUPPLY AND DRAIN |
| | BOX THAT WILL PROTECT THE INTEGRITY OF THE RATED WALL. |
| | WPB FBC 107.2.1 |
| | C) PROVIDE WATER HAMMER ARRESTORS AT THE WASHING |
| | MACHINE PER FBC PL 604.9. |
| | 2 .PROVIDE UL ASSEMBLIES FOR HORIZONTAL WATER, WASTE |
| | AND VENT PENETRATIONS FOR THE 1 HR FIRE RATED WALL IN |
| | THE BACK ROOM. WPB FBC 107.2.1 |
| | 3. PROVIDE UL LISTED ACCESS PANELS FOR IN-WALL VALVES |
| | AND TMV IN 1HR FIRE RATED WALL AT BACK ROOM. |
| | 4. IS THE EXISTING WOMEN?S REST ROOM TO BE ADA |
| | COMPLIANT? IF SO, INDICATE ON THE PLANS AS ADA. WPB FBC |
| | 107.2.1 |
| | 5. RE: PLAN PAGE P3; INSTA-HOT PIPING DETAIL. |
| | A) PROVIDE A FULL OPEN SUPPLY VALVE FOR THE WATER |
| | HEATER PER FBC PL 606.1.8. THREE-WAY ANGLE STOP SERVING |
| | THE SINK AND THE WATER HEATER IS PROHIBITED. |
| | 6. WATER RISER DIAGRAM SHOWS TMV AT THE WATER HEATER. |
| | WATER HEATER DETAIL DOES NOT SHOW TMV. PLEASE CLARIFY. |
| | ADDITIONALLY, THE WATER RISER DIAGRAM SHOWS IN-WALL |
| | TMVS AT INDIVIDUAL FIXTURES. PLEASE CLARIFY. IN-WALL |
| | VALVES AND TMVS REQUIRE ACCESS PANELS. PLEASE SPECIFY. |
| | WPB FBC 107.2.1 |
| | 7. WATER RISER DIAGRAM SHOWS PAN AND DRAIN FOR THE |
| | WATER HEATER. WATER HEATER DETAIL DOES NOT. PLEASE |
| | CLARIFY. WPB FBC 107.2.1 |
| | 8. RE: PLAN PAGE P3; WASHING MACHINE DETAIL. |
| | A) PROVIDE WATER HAMMER ARRESTORS AT THE WASHING |
| | MACHINE PER FBC PL 604.9. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |