Plan Review Notes
Plan Review Notes For Permit 18100991
Permit Number 18100991
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-26 08:49:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18100991
 ADD: 901 N FLAGLER DR. SUITES: 1 & 2
 CONT: PAGE CONTRACTING
 TEL: 954-868-4561
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 26/2018
 ACTION: DENIED
  
 1) SHEET A2.01:
 1A) SHEET A2.01 SHOWS A BREAKROOM WITH MICROWAVE AND A
 CUT SECTION 2D/A8.02. SHEET A8.20 DOES SHOW A CUT
 SECTION D THROUGH THE BREAKROOM CABINET DETAIL, BUT
 THERE IS NO SECTION SHOWING THE PLACEMENT OF THE
 MICROWAVE. IN THE LOWER CABINETS, OR ON THE COUNTER TOP
 OR IS IT ON A SHELF IN THE UPPER CABINETS.
 SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 1B) THE PLAN INDICATES THIS IS A BUSINESS OCCUPANCY
 WITH 2 AREAS LABELED PIT, THE PLANS ARE SILENT AS TO
 WHAT THIS AREA IS TO BE USED FOR, THERE IS NO CHAIRS,
 TABLES OR KIOSK PLEASE PROVIDE ADDITIONAL INFORMATION,
 IT MAY AFFECT TRAVEL DISTANCES, OR OCCUPANT LOADS?
 107.2.2.1. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) SHEET A2.01 DOES INDICATE THE ARCHITECT IS
 MAINTAINING A 1 HOUR TENANT SEPARATION WALL BETWEEN THE
 EXISTING TENANT AND PROPOSED TENANT SPACE. A POINT OF
 CLARIFICATION NEEDS TO OCCUR BETWEEN A2.01 AND SHEET
 M1. AND M2. SHEET M2 MOUNTING DETAIL SHOWS A FRESH AIR
 DUCT WITH MOTORIZED DAMPER. SHEET M1 SHOWS WHAT APPEARS
 TO BE THE FRESH AIR DUCT WITHIN THE 1 HOUR FIRE RATED
 WALL AN UP THROUGH THE WALL AND THROUGH THE ROOF. THE
 PLAN DOES NOT SHOW COMPLIANCE WITH SECTION 714.3.2
 MEMBRANE PENETRATIONS OF THE 2017 FBC-B. MEMBRANE
 PENETRATIONS SHALL COMPLY WITH SECTION 714.3.1, WHERE
 WALLS OR PARTITIONS ARE REQUIRED TO HAVE
 FIRE-RESISTANCE RATINGS.
 PLEASE ALSO NOT IF THE FRESH AIR DUCT IS WITHIN THE A/C
 CLOSET AND THE FRESH AIR DUCT DOES NOT PENETRATE THE
 ONE HOUR FIRE RATED WALL, THEN NO FIRE DAMPER IS
 REQUIRED. CLARIFICATION IS REQUIRED. 107.2.2.1
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  