Plan Review Notes
Plan Review Notes For Permit 18100987
Permit Number 18100987
Review Stop B
Sequence Number 2
Notes
Date Text
2018-10-30 13:19:03RESIDENTIAL (R2) FLOORING SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- INFORMATION SUBMITTED FOR PROFLEX 90 MSC ARE NOT THE
 COPIES OF THE REQUIRED TESTING. INFORMATION SUBMITTED
 IS ONLY THE MANUFACTURER'S SPECS. WE NEED COPIES OF THE
 ACTUAL TESTING THAT MATCHES THIS BUILDING CONSTRUCTION.
 IN ADDITION, THE INFORMATION SUBMITTED IS FOR BUILDINGS
 WITH 8" CONCRETE SLAB THICKNESS WITH AN ACOUSTICAL
 CEILING ASSEMBLY. TYPICALLY, THERE ARE NO BUILDINGS
 WITH SUSPENDED ACOUSTICAL CEILINGS IN THIS AREA. PLEASE
 SUBMIT THE INFORMATION REQUESTED IN THE FIRST REVIEW.
 SEE BELOW.
  
 1- FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]