| 2018-10-30 13:19:03 | RESIDENTIAL (R2) FLOORING SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- INFORMATION SUBMITTED FOR PROFLEX 90 MSC ARE NOT THE |
| | COPIES OF THE REQUIRED TESTING. INFORMATION SUBMITTED |
| | IS ONLY THE MANUFACTURER'S SPECS. WE NEED COPIES OF THE |
| | ACTUAL TESTING THAT MATCHES THIS BUILDING CONSTRUCTION. |
| | IN ADDITION, THE INFORMATION SUBMITTED IS FOR BUILDINGS |
| | WITH 8" CONCRETE SLAB THICKNESS WITH AN ACOUSTICAL |
| | CEILING ASSEMBLY. TYPICALLY, THERE ARE NO BUILDINGS |
| | WITH SUSPENDED ACOUSTICAL CEILINGS IN THIS AREA. PLEASE |
| | SUBMIT THE INFORMATION REQUESTED IN THE FIRST REVIEW. |
| | SEE BELOW. |
| | |
| | 1- FLOORING SOUND INSULATION MATERIAL: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| | (2017). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND |
| | PROPOSED FLOOR FINISH. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |