| 2018-10-24 08:50:12 | 1) A PRESSURE VACUUM BREAKER ASSEMBLY IS NOT PERMITTED | | | ON A NON-RESIDENTIAL IRRIGATION SYSTEM PER THE CITY OF | | | WEST PALM CROSS-CONNECTION CONTROL MANUAL. THE MINIMUM | | | LEVEL OF PROTECTION IS A REDUCED PRESSURE ZONE VALVE | | | ASSEMBLY. | | | 2) ALL DEVICES MUST BE LEAD FREE AND APPROVED BY THE | | | FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC | | | RESEARCH AT THE UNIVERSITY OF SOUTHERN CALIFORNIA. | | | 3) AS AN FYI - ALL NEW DEVICES MUST BE TESTED AND | | | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES | | | DEPT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|