Plan Review Notes
Plan Review Notes For Permit 18100971
Permit Number 18100971
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-24 08:50:121) A PRESSURE VACUUM BREAKER ASSEMBLY IS NOT PERMITTED
 ON A NON-RESIDENTIAL IRRIGATION SYSTEM PER THE CITY OF
 WEST PALM CROSS-CONNECTION CONTROL MANUAL. THE MINIMUM
 LEVEL OF PROTECTION IS A REDUCED PRESSURE ZONE VALVE
 ASSEMBLY.
 2) ALL DEVICES MUST BE LEAD FREE AND APPROVED BY THE
 FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC
 RESEARCH AT THE UNIVERSITY OF SOUTHERN CALIFORNIA.
 3) AS AN FYI - ALL NEW DEVICES MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW