| 2018-12-03 11:48:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLAN SHEETS ARE TOO SMALL AND |
| | UNREADABLE AND AS A RESULT AN OFFICIAL PLAN REVIEW CAN |
| | NOT BE COMPLETED WITH ANY ACCURACY OR CONFIDENCE. |
| | |
| | PLEASE ENLARGE AND RESUBMIT |
| | |
| | |
| | 2ND RESPONSE: |
| | |
| | THE PLANS REMIAN TOO SMALL. IN ADDITION, ONLY ONE SHEET |
| | WAS SUBMITTED. A MINIMUM OF TWO PLAN SHEETS ARE |
| | REQUIRED. |
| | |
| | |
| | |
| | |
| | |
| | 2) A SCOPE OR WORK COULD NOT BE IDENTIFIED. IS THIS A |
| | FIRE LINE ASSEMBLY? IS IT A NEW INSTALL? IS THIS A |
| | RELOCATION? |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND SCOPE OF |
| | WORK. |
| | |
| | |
| | |
| | 2ND RESPONSE: |
| | |
| | THE STATED RESPONSE DOES NOT INDICATE IF THIS IS JUST A |
| | DOCV. IF NEW FIRE LINE IS PROPOSED WITH THE DOCV, HOW |
| | LONG IS IT AND PROVIDE THE APPLICABLE SPECIFICATION |
| | SHEETS. |
| | |
| | |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF COMPLIANCE WITH NFPA 24 |
| | STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE |
| | MAINS AND THEIR APPURTENANCES 2013 EDITION, IF |
| | APPLICABLE PER # 2. |
| | |
| | PLEASE ENSURE COMPLIANCE WITH, BUT NOT LIMITED TO, |
| | |
| | 6.5 BACKFLOW PREVENTION ASSEMBLIES. |
| | 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW |
| | PREVENTION |
| | ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR |
| | INSTALLATION INSTRUCTIONS. |
| | 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED, |
| | THEY |
| | SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE |
| | NEEDED. |
| | |
| | 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| | FOR FIRE |
| | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| | ONE |
| | OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FT (12 M) |
| | FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR |
| | VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH |
| | SECTION 6.4 |
| | (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT |
| | LESS THAN 40 FT (12 M) FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | BACKFLOW |
| | PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL |
| | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | |
| | |
| | 2ND RESPONSE: |
| | |
| | THE EXISITNG BOLLARDS COMMENT IS ACCEPTED. |
| | |
| | UNDER SECTION (4) (A) A 4"GATE VALVE IS INSTALLED DOES |
| | NOT MEET THE REQUIREMENT OF THIS CODE. |
| | |
| | THE PROPOSED DOCV AS WELL A THE GATE VALVE IS CLOSER |
| | THAN 40' FROM THE BUILDING BUT STILL REMIANS WITHIN THE |
| | HEIGHT OF THE BUILDING. IN ADDITION THERE ARE NO SPEC |
| | SHEETS FOR THE GATE VALVE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |