| Plan Review Notes For Permit 18100841 |
| Permit Number |
18100841 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-19 17:19:27 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | CONTRACTOR NOT LICENSED FOR THIS TYPE OF WORK CVC FOR | | | SOLAR WORK ONLY NOT TO CHANGE A SERVICE AND ADD | | | BATTERIES TO A SERVICE. | | | | | | 61G4-15.021 CERTIFICATION OF SOLAR CONTRACTORS. | | | | | | (A) ELECTRICAL WORK. THE BRANCH CIRCUIT SUPPLYING THE | | | ELECTRIC WATER HEATER, THE RECEPTACLE OUTLET FOR A | | | CORD-AND-PLUG-CONNECTED SOLAR CONTROLLER, THE SWIMMING | | | POOL PUMP MOTOR, AND THE | | | PREMISES WIRING ON THE LOAD SIDE OF THE PREMISES | | | SERVICE DISCONNECTING MEANS SHALL BE IN ACCORDANCE WITH | | | THE NATIONAL ELECTRIC CODE. IF INSTALLATION, | | | ALTERATION, REMOVAL, REPLACEMENT, | | | OR UPGRADING OF THIS CIRCUIT IS NECESSARY, THE WORK | | | SHALL BE PERFORMED BY LICENSED ELECTRICAL CONTRACTORS | | | ONLY. | | | | | | BATTERIES FOR SYSTEM ARE THEY LOCATED IN THE ECO 10 | | | CABINET 690.71 | | | | | | GROUNDING OF SERVICE SHOWN WRONG ON PLAN FIRST MEANS OF | | | DICONNECT IS THE ECO 10 UNIT. NEUTRAL BONDING AND | | | GROUNDING ELECTRODE SHOULD OCCUR IN THE ECO 10 CABINET. | | | 250.24(C) | | | | | | PANELBOARD INSIDE SHALL ALL NEUTRALS AND GROUNDS | | | SEPARATED. | | | | | | | | | | | | |
|